BLACK_BUILDING_TEST

Full-site power-fail drill: utility open, ride-through on battery, generator pickup, soak and return to utility.

Validated application blockDCIM · ReliabilityIEC 61131-3v1.0.0

When to use it

Use BLACK_BUILDING_TEST when the site's annual or semi-annual black-building test has to be run as a controlled sequence — utility opened deliberately, load riding on UPS, generators picking up, soak, and a proven return — with an automatic abandon if the load is not picked up in time.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL—
STARTBOOL—
ABORTBOOL—
MAX_ON_BATTTIME—
STEP_TIMEOUTTIME—
SOAK_TIMETIME—
GEN_LOSS_DEBTIME—
RESTORE_TMOTIME—
PRECHECK_OKBOOL—
UTIL_CLOSED_FBBOOL—
UTIL_OPEN_FBBOOL—
ON_BATT_FBBOOL—
GEN_LOAD_FBBOOL—
UPS_RUNTIME_MINREALmin
MIN_RESERVE_MINREALmin
ACKBOOL—

Outputs

PortTypeUnit
STEPUSINT—
TOTAL_STEPSUSINT—
RUNNINGBOOL—
RESTORINGBOOL—
UTIL_OPEN_CMDBOOL—
UTIL_CLOSE_CMDBOOL—
GEN_START_CMDBOOL—
STEP_OKBOOL—
PASSEDBOOL—
FAILEDBOOL—
ABORTEDBOOL—
GEN_PICKUP_SREALs
ON_BATT_SREALs
RESTORE_ELAPSED_SREALs
STEP_ELAPSED_SREALs
ALM_BATT_TIME_EXCEEDEDBOOL—
ALM_GEN_LOSTBOOL—
ALM_RESTORE_FAILEDBOOL—
ALM_STEP_TMOBOOL—
ALM_RESERVE_LOWBOOL—

Supervised control write

BLACK_BUILDING_TEST commands a real actuator. It is written to sit underneath your own interlock, permissive and protection logic — not to replace it. Commission it as you would any control block you wrote yourself.

Validation evidence

Tests
10
Simulated scans
210
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3

Download BLACK_BUILDING_TEST — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML and the datasheet.

Every block in the catalogue is free to download, in every format it ships, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.

Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.