BIOREACTOR_TEMP_CTRL

Bioreactor jacket temperature control, split-range heat/cool with a jacket low-temperature limit.

Validated application blockLS · BioreactorIEC 61131-3IEC 61499v1.0.0

When to use it

Use BIOREACTOR_TEMP_CTRL when a jacketed bioreactor or fermenter holds broth temperature with a heating service and a cooling service on the same jacket, and the vessel wall must not be driven below the temperature the culture tolerates.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
TEMPREALdegC
TEMP_OKBOOL
SPREALdegC
JACKET_TREALdegC
JACKET_T_OKBOOL
JACKET_MINREALdegC
JACKET_HYSTREALK
KPREAL%/K
TIREALs
SPLIT_DBREAL%
HEAT_MAXREAL%
COOL_MAXREAL%
DEV_ALM_KREALK
DEV_TMOTIME
ACKBOOL

Outputs

PortTypeUnit
HEAT_PCTREAL%
COOL_PCTREAL%
DEV_KREALK
IN_BANDBOOL
VALIDBOOL
ALM_DEVBOOL
ALM_T_FAULTBOOL
ALM_JACKET_FAULTBOOL
ALM_JACKET_LIMITBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
9
Simulated scans
234
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download BIOREACTOR_TEMP_CTRL — free