BE1_50_IOC

Basler-shaped instantaneous / definite-time overcurrent high-set (ANSI 50) with dropout ratio and a sealed trip.

Validated application blockPSUB·BaslerIEC 61131-3IEC 61499v1.0.0

When to use it

Use BE1_50_IOC when a high-set element is needed to clear close-in faults without waiting for the inverse-time curve — typically set at 6 to 10 times nominal so it sees only faults inside the protected section.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
IaREALpu
IbREALpu
IcREALpu
IpuREALpu
T_SETTIME
DO_RATIOREALpu
CT_OKBOOL
BLKBOOL
ACKBOOL

Outputs

PortType
TRIPBOOL
opBOOL
BLOCKEDBOOL
ALM_CT_FAILBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Supervised control write

BE1_50_IOC commands a real actuator. It is written to sit underneath your own interlock, permissive and protection logic — not to replace it. Commission it as you would any control block you wrote yourself.

Validation evidence

Tests
7
Simulated scans
76
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download BE1_50_IOC — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML, the IEC 61499 function block type (.fbt) and the datasheet.

Every block in the catalogue is free to download, in every format, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.

Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.