Basler-shaped under / over-voltage element (ANSI 27/59) with definite-time delay, reset hysteresis, dead-bus discrimination and VT-failure blocking.

Validated application blockPSUB·BaslerIEC 61131-3IEC 61499v1.0.0

When to use it

Use BE1_27_59_V when a bus, generator terminal or motor feeder needs under-voltage and over-voltage stages that ride through momentary sags and swells, and must not trip on a blown VT fuse or a bus that is simply de-energised.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
VaREALpu
VbREALpu
VcREALpu
V27REALpu
V59REALpu
tDTIME
EN27BOOL
EN59BOOL
HYST_PCTREAL%
V_DEADREALpu
BKR_CLOSEDBOOL
VT_OKBOOL
BLKBOOL
ACKBOOL

Outputs

PortType
UVBOOL
OVBOOL
TRIPBOOL
TRIP27BOOL
TRIP59BOOL
BUS_DEADBOOL
DEAD_INHBOOL
BLOCKEDBOOL
ALM_VT_FAILBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Supervised control write

BE1_27_59_V commands a real actuator. It is written to sit underneath your own interlock, permissive and protection logic — not to replace it. Commission it as you would any control block you wrote yourself.

Validation evidence

Tests
8
Simulated scans
214
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499