BE1_25_SYNC

Basler-shaped synchronism-check element (ANSI 25) issuing a close permissive on breaker-close-time-compensated phase angle, with dead-line and dead-bus options.

Validated application blockPSUB·BaslerIEC 61131-3v1.0.0

When to use it

Use BE1_25_SYNC when a breaker paralleling two energised sources must only be closed when the two sides are close enough in voltage, frequency and phase, and where a dead-line or dead-bus close is separately permitted.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL—
VlineREALpu
VbusREALpu
dPhiREALdeg
dFREALHz
dVREALpu
dPhiMaxREALdeg
dFmaxREALHz
dVmaxREALpu
VliveREALpu
VdeadREALpu
CB_TIMEREALs
T_SYNCTIME—
EN_DLLBBOOL—
EN_LLDBBOOL—
EN_DLDBBOOL—
DEAD_SUP_LBOOL—
DEAD_SUP_BBOOL—
CLOSE_REQBOOL—
SYNC_TMOTIME—
VT_OKBOOL—
BLKBOOL—
ACKBOOL—

Outputs

PortTypeUnit
PERMITBOOL—
IN_WINDOWBOOL—
inSyncBOOL—
PHI_PREDREALdeg
LIVE_LINEBOOL—
LIVE_BUSBOOL—
DEAD_PERMITBOOL—
BLOCKEDBOOL—
ALM_SYNC_TMOBOOL—
ALM_VT_FAILBOOL—
ALM_CFG_ERRBOOL—

Validation evidence

Tests
11
Simulated scans
163
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3

Download BE1_25_SYNC — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML and the datasheet.

Every block in the catalogue is free to download, in every format it ships, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.

Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.