BATTERY_MON

Starting-battery and charger supervision with a crank volt-drop test, crank-inhibited low-voltage alarm and latched charger failure.

Validated application blockGen · EngineIEC 61131-3IEC 61499v1.1.0

When to use it

Use BATTERY_MON when a generator set's starting battery and its float charger have to be supervised between runs — the NFPA 110 battery-charger-failure and low-battery-voltage alarms — and a weak battery must be caught by the volt drop it shows under crank rather than by a failure to start.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
VDCREALV
VDC_OKBOOL
LOW_VREALV
HIGH_VREALV
V_HYSTREALV
CRANK_MIN_VREALV
CHG_AC_OKBOOL
ENGINE_RUNBOOL
CRANKINGBOOL
ALM_DLYTIME
CRANK_RECOVER_TTIME
ACKBOOL

Outputs

PortTypeUnit
CHARGER_FAILBOOL
ALM_LOW_VBOOL
ALM_HIGH_VBOOL
ALM_WEAK_BATTBOOL
ALM_VDC_FAULTBOOL
ALM_CFG_ERRBOOL
BATT_OKBOOL
CRANK_MIN_VDCREALV

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
13
Simulated scans
197
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download BATTERY_MON — free