AUTO_SYNC

Automatic synchroniser: AVR and governor bias trimming, and a close permissive advanced by the breaker's own closing time.

Validated application blockGen · SynchronizationIEC 61131-3v1.0.0

When to use it

Use AUTO_SYNC when a generator has to be brought into step with a live bus without an operator on the synchroscope — the controller trims excitation and speed until the machine matches, then issues one close command timed so the machines are in phase when the contacts touch.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL—
REQBOOL—
ABORTBOOL—
GEN_VREALpu
GEN_FREALHz
GEN_ANGREALdeg
BUS_VREALpu
BUS_FREALHz
BUS_ANGREALdeg
MEAS_OKBOOL—
DV_MAXREALpu
SLIP_MAXREALHz
ANG_WINREALdeg
TCBTIME—
LIVE_PUREALpu
SLIP_TGTREALHz
KVREAL%/pu
KFREAL%/Hz
V_BIAS_MAXREAL%
F_BIAS_MAXREAL%
LOCK_TTIME—
CLOSE_PWTIME—
SYNC_TMOTIME—
ACKBOOL—

Outputs

PortTypeUnit
V_BIASREAL%
F_BIASREAL%
LOCKEDBOOL—
CLOSE_PERMBOOL—
SLIPREALHz
DANGREALdeg
DVREALpu
ADV_DEGREALdeg
ANG_AT_CLOSEREALdeg
DV_OKBOOL—
SLIP_OKBOOL—
ANG_OKBOOL—
BOTH_LIVEBOOL—
VALIDBOOL—
ALM_SYNC_FAILBOOL—
ALM_MEAS_FAULTBOOL—
ALM_CFG_ERRBOOL—

Supervised control write

AUTO_SYNC commands a real actuator. It is written to sit underneath your own interlock, permissive and protection logic — not to replace it. Commission it as you would any control block you wrote yourself.

Validation evidence

Tests
12
Simulated scans
229
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3

Download AUTO_SYNC — free

Create a free Ri Tech account to download the block. You get the Structured Text body, the Rockwell Add-On Instruction (.L5X), the Schneider Control Expert DFB (.XDB), PLCopen XML and the datasheet.

Every block in the catalogue is free to download, in every format it ships, with no purchase and no card. Browsing needs no account at all; downloading needs a signed-in one, so the block lands in your library and re-downloads whenever you need it.

Source is never published on this page. The implementation is released to a signed-in Ri Tech account — free of charge, but never anonymously.