AERATION_DO_CTRL

Aeration zone dissolved-oxygen control on the zone air valve, publishing the zone's air demand for the blower header and failing to a fixed valve position on probe loss.

Validated application blockW/WW · Treatment ProcessIEC 61131-3IEC 61499v1.0.0

When to use it

Use AERATION_DO_CTRL when an activated-sludge aeration zone holds dissolved oxygen with its own modulating air valve, and the zone's air demand has to be published upward to a most-open-valve blower control.

Interface

The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.

Inputs

PortTypeUnit
ENABLEBOOL
DO_PVREALmg/L
DO_OKBOOL
DO_SPREALmg/L
V_MINREAL%
V_MAXREAL%
FAIL_PCTREAL%
KPREAL%/(mg/L)
TI_SREALs
AIR_MAXREALNm3/h
DO_LOWREALmg/L
DO_HIGHREALmg/L
LOW_PERSIST_TTIME
ACKBOOL

Outputs

PortTypeUnit
VALVE_PCTREAL%
AIR_DEMANDREALNm3/h
DO_ERRREALmg/L
AT_LIMITBOOL
VALIDBOOL
ALM_DO_LOWBOOL
ALM_DO_HIGHBOOL
ALM_PROBE_FAULTBOOL
ALM_CFG_ERRBOOL

IEC 61499 event interface

EI INIT, REQ·EO INITO, CNF

Validation evidence

Tests
7
Simulated scans
580
Simulator
v0.1.0

Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.

  • Conforms to IEC 61131-3
  • Conforms to IEC 61499

Download AERATION_DO_CTRL — free