ABB_ACQ580_PUMP
ABB ACQ580 water/wastewater drive — ABB Drives profile telegram driver with speed limits and PLC-side low-demand sleep, and no jog.
When to use it
Use ABB_ACQ580_PUMP when an ACQ580 water or wastewater drive is controlled over a fieldbus using the ABB Drives communication profile — a lift-station pump, a transfer or booster set, a filter feed — and the PLC owns the run/stop decision and the speed limits.
Interface
The published port signature. This is the whole of what the block exposes to your program — the implementation body is not shown here and ships with the download.
Inputs
| Port | Type | Unit |
|---|---|---|
| ENABLE | BOOL | — |
| RUN | BOOL | — |
| SPD_REF | REAL | % |
| SPD_MIN | REAL | % |
| SPD_MAX | REAL | % |
| SLEEP_LVL | REAL | % |
| SLEEP_DLY | TIME | — |
| WAKE_BAND | REAL | % |
| RAMP_HOLD | BOOL | — |
| RAMP_TO_ZERO | BOOL | — |
| COAST_STOP | BOOL | — |
| EMCY_STOP | BOOL | — |
| FAULT_RESET | BOOL | — |
| STATUS_WORD | WORD | — |
| ACT1_WORD | INT | — |
| ACT_FULL_SCALE | INT | — |
| FAULT_CODE_WORD | UINT | — |
| COMMS_OK | BOOL | — |
| TELEGRAM_TMO | TIME | — |
| REF_SCALED | BOOL | — |
| START_TMO | TIME | — |
| STOP_HOLD | TIME | — |
| ACK | BOOL | — |
Outputs
| Port | Type | Unit |
|---|---|---|
| CTRL_WORD | WORD | — |
| REF1_WORD | INT | — |
| SPEED_PCT | REAL | % |
| SPD_ACT_PCT | REAL | % |
| SEQ_STATE | INT | — |
| READY | BOOL | — |
| RUNNING | BOOL | — |
| AT_SETPOINT | BOOL | — |
| ST_RDY_RUN | BOOL | — |
| ST_SWON_INHIBITED | BOOL | — |
| ST_REMOTE | BOOL | — |
| SLEEPING | BOOL | — |
| FAULT_CODE | UINT | — |
| ALM_TRIPPED | BOOL | — |
| ALM_WARNING | BOOL | — |
| ALM_OFF2_ACTIVE | BOOL | — |
| ALM_OFF3_ACTIVE | BOOL | — |
| ALM_TELEGRAM_STALE | BOOL | — |
| ALM_START_TMO | BOOL | — |
| ALM_LOCAL | BOOL | — |
| ALM_REF_UNSCALED | BOOL | — |
| ALM_REF_CLAMPED | BOOL | — |
| ALM_CFG_ERR | BOOL | — |
IEC 61499 event interface
EI INIT, REQ·EO INITO, CNF
Supervised control write
ABB_ACQ580_PUMP commands a real actuator. It is written to sit underneath your own interlock, permissive and protection logic — not to replace it. Commission it as you would any control block you wrote yourself.
Validation evidence
- Tests
- 23
- Simulated scans
- 499
- Simulator
- v0.1.0
Complete IEC 61131-3 implementation with a published test suite that runs on the vplant simulator. The counts above are that suite, executed on this build.
- Conforms to IEC 61131-3
- Conforms to IEC 61499